FD113-ZU[K] OIL PRESSURE SAFETY CONTROLS
Pressure
Range adjustable from 4 to 65 PSID; Timer start pressure–timer
stop pressure is 3 PSID above timer start pressure
A
SPDT switch is used in the pressure portion of the control which
allows the addition of a "safe light" if desired
Electronic
Timer is Time-Adjustable from 20 to 150 seconds
Supply
voltage—24 to 240 Volt AC/DC; Timing unaffected
by voltage or ambient temperature variations
A
SPDT Manual Reset Switch is used in the Timer Module; Upon
time-out, the compressor is stopped and an alarm circuit
is energized; To restart the compressor and de– energize
the alarm circuit, the reset button is pushed
A
factory installed Jumper allows the FD113 to be powered from
a single power source; Should separate circuits be desired
for the timer and "Lockout" switch, the Jumper can
be remove
|